R46/2012-A-CN2-26.08
OIML CERTIFICATE
ISSUED UNDER SCHEME A
OIML Issuing Authority Name: National Institute of Metrology, China Address: No.18, Bei San Huan Dong Lu, Chaoyang Dist., Beijing, P. R. China Person responsible: Mr. Li Wentao
Applicant Name: Inhemeter Co., Ltd.
Address: 8/F&9/F, 1A, Software Park, Southern Hi-Tech Zone, Nanshan District,
518054 Shenzhen, P. R. China
Manufacturer Name: Inhemeter Co., Ltd.
Address: 8/F&9/F,1A,Software Park,Southern Hi-Tech Zone,Nanshan District,
518054 Shenzhen,P.R. China
Identification of the Single Phase Smart Energy Meter certified type i100,220 V,0.25-0.5(80) A,50 Hz (Further characteristics on page 2)
This OIML Certificate attests the conformity of the above identified type (represented by the sample(s) identified in the OIML type evaluation report) with the requirements of the following Recommendation of the International Organization of Legal Metrology (OIML):
OIML R46 - Edition 2012
For accuracy class: Class B
This OIML Certificate relates only to metrological and technical characteristics of the type of measuring instrument covered by the relevant OIML Recommendation identified above.
This OIML Certificate does not bestow any form of legal international approval.
Important note: Apart from the mention of the Certificate's reference number and the name of the OIML Member State in which the Certificate is issued, partial quotation of the Certificate and of the associated OIML type evaluation report(s) is not permitted, although either may be reproduced in full.
OIML Issuing Authority:
Date:
National Institute of Metrology, China
26 June 2026
OIML Issuing Authority
中国OIML证书发证机构
No.18, Bei San Huan Dong Lu, Chaoyang Dist, Beijing, 100029, P.R.China +861064525646 oimlia@nim.ac.cn www.nim.ac.cn
Li Wentao
Director
National Institute of Metrology, China
| OIML Member State | OIML Certificate No. |
| P. R. China | R46/2012-A-CN2-26.08 |
The conformity was established by the results of tests and examinations provided in the associated OIML type evaluation report:
No. TER-R46/2012-CN2-26.08 dated 23 June 2026 that includes 24 pages
and the associated OIML test report:
No. ZQS-NJDLO-2026060001 dated 15 June 2026 that includes 79 pages
OIML Certificate History
| Revision No. | Date | Description of the modification |
| 0 | 26 June 2026 | Initial issue |
Characteristics of the Instrument
| Meter type(electromechanical/static): | Static |
| Accuracy class: | Class B |
| Nominal voltage, $U_{\mathrm{nom}}$: | 220V |
| Nominal frequency,$f_{\mathrm{nom}}$: | 50Hz |
| Maximum current,$I_{\mathrm{max}}$: | 80A |
| Transitional current,$I_{\mathrm{tr}}$: | 0.5A |
| Minimum current,$I_{\mathrm{min}}$: | 0.25A |
| Starting current,$I_{\mathrm{st}}$: | 0.02A |
| Connection mode(phases,wires,elements): | Direct-connected,One phase two wires,one element |
| Direction of energy flow/registers: | Two-register,bi-directional |
| Register multiplier: | 1 |
| Meter constant: | 1000imp/kWh |
| Specified clock frequencies: | Energy measuring chip:6MHz,MCU:32.768kHz |
| Indoor/Outdoor: | Outdoor |
| IP Rating: | IP54 |
| Terminal arrangement(e.g:BS,DIN): | BS |
| Insulation protection class: | II |
| Lower specified temperature: | -25℃ |
| Upper specified temperature: | +55℃ |
| Humidity class: | H3 |
| Tilt/Mounting position: | Any position is allowed |
| Hardware version(s): | INHE-i100-h5g-0c01-CA1-A1-20251023INHE-i100-h5g-0c01-C02-A1-20251023INHE-i100-h5g-0c01-CA3-A2-20251217INHE-i100-h5g-0b01-C04-A0.1-20250624 |
| Software version(s): | DKF3-0A-24062401;checksum:780A9D18. |
Remarks:
Communication interfaces: Basic: 1 Optical port, 1 Bluetooth.
Extended: 1 4G Module, 1 G3-Hybrid Module, 1 G3 PLC Module, 1 HPLC+HRF Module.