Skip to content

← R137

R137/2012-A-NL1-20.07 Rev. 2

Applicant
Elster GmbH
Issuer
NL1
Issuing year
2022
Status
Valid

Source PDF (certificates/R137/2012/r137-2012-nl1-2020-07-rev2.pdf) · extracted by OCR from the digitalized tier of the corpus.

R137/2012-A-NL1-20.07 Rev. 2

OIML Certificate

OIML Member State The Netherlands

Number R137/2012-A-NL1-20.07 revision 2 Project number 3572038 Page 1 of 6

Issuing authority Person responsible:

Applicant and Manufacturer

NMi Certin B.V.

M.Ph.D. Schmidt

Elster GmbH

Steinern Straße 19-21

55252 Mainz-Kastel

Germany

Identification of the certified type

An Ultrasonic Gas Meter Type: Q.Sonic $ ^{m a x} $

Characteristics

See page 2 and further

This OIML Certificate is issued under scheme A.

This Certificate attests the conformity of the above identified type (represented by the sample(s) identified in the OIML Type Evaluation Report) with the requirements of the following Recommendation of the International Organization of Legal Metrology (OIML):

R 137-1:2012 "Gas meters"

Accuracy class 0,5

This Certificate relates only to the metrological and technical characteristics of the type of measuring instrument covered by the relevant OIML International Recommendation identified above. This Certificate does not bestow any form of legal international approval.

This certificate and supporting reports comply with the requirements of OIML-CS-PD-07 clause 6.2.

Important note: Apart from the mention of the Certificate's reference number and the name of the OIML Member State in which the Certificate was issued, partial quotation of the Certificate and of the associated OIML Type Evaluation Report(s) is not permitted, although either may be reproduced in full.

Issuing Authority

NMi Certin B.V., OIML Issuing Authority NL1 18 August 2022

NMi Certin B.V.

Thijsseweg 11

2629 JA Delft

The Netherlands

T +31 88 636 2332

certin@nmi.nl

www.nmi.nl

Certification Board

This document is issued under the provision that no liability is accepted and that the applicant shall indemnify third-party liability.

The notification of NMi Certin B.V. as Issuing Authority can be verified at www.oiml.org

This document is digitally signed and sealed. The digital signature can be verified in the blue ribbon at the top of the electronic version of this certificate.

OIML Certificate

OIML Member State The Netherlands

Number R137/2012-A-NL1-20.07 revision 2 Project number 3572038 Page 2 of 6

The conformity was established by the results of tests and examinations provided in the associated reports:

  • No. NMi-9200288-01 dated 18 January 2012 that includes in total 48 pages;

  • No. NMi-16200535-01 revision 1 dated 1 September 2017 that includes 35 pages;

  • No. NMi-1902121-01 dated 12 October 2018 that includes 14 pages.

  • No. NMi-2326650-01 dated 12 October 2020 that includes 20 pages.

  • No. NMi-2500011-01 dated 29 June 2021 that included 21 pages.

Characteristics of the measuring instrument

In Table 1 the general characteristics of the measuring instrument are presented.

Table 2 gives an overview of the software versions of the electronics.

Table 3 gives an overview of the general characteristics of the family of instruments.

The construction of the measuring instrument is recorded in the Documentation folder no. T10586-3.

Table 1 General characteristics

Destined for the measurement ofGas volume
Environmental classesM1/E2
Accuracy class0,5
Working pressureThe meter is either programmed with a density and viscosity setting, corresponding to the applied gas at preset pressure or using live pressure value from the optional pressure sensor. When using a preset value, the maximum operating range for pressure $ p_{\mathrm{max}}/p_{\mathrm{min}} $ is 6,25 symmetrically divided around the preset pressure.
Ambient temperature range-40-+70 $ ^{\circ}C $ gas meter-40-+55 $ ^{\circ}C $ gas meter with EVCD
Gas temperature range-40-+100 $ ^{\circ}C $ gas meter-30-+80 $ ^{\circ}C $ gas meter with EVCD
Designed forNon-condensing humidity and condensing humidity
OrientationHorizontal; vertical up; vertical down and all orientations.
Power supply voltage18-30V DC

OIML Certificate

OIML Member State The Netherlands

Number R137/2012-A-NL1-20.07 revision 2

Project number 3572038

Page 3 of 6

Table 2 Software identification

Software partSoftware versionChecksumSoftware versionChecksum
NGQFB01.00.06 01.00.070x8A36A8B7 0xB756810701.00.080x350616D6
NGQMB01.00.08 01.00.100x81905758 0x0C432F9701.00.120xD8615DF7
Basic system02.08.00.0029 02.10.01.0003 02.11.00.00180xEBF74980 0x7C01880E 0x7557458803.02.00.0000 03-40-A0x36B6BE1E 0x0EA0B879
Density & Viscosity02.04.00.0000 02.04.00.0001 02.04.00.00050x804BDA24 0xBB87257F 0x1DF2525D03.00.00.0000 03-01-A0xE062B4B9 0xA5C2AE67
Geometry Correction02.04.00.0000 02.04.00.0001 02.05.00.00000x90D4BD88 0xD8D14A5F 0x6C1DF99103.00.00.0000 03-01-A0x4F26E00E 0xFD14CF91
USM02.08.00.0000 02.10.00.0000 02.11.00.00180x57D99098 0x3DE0303F 0x9B8E623403.02.00.0000 03-03-A0x46340214 0xC1006EAD
Gas Quality02-09-B 02-09-C 02-09-D0x31D9C769 0xC83315E2 0xBD08315803-13-A 03-15-F0x98B1FD23 0x05CB4161
Flow Conversion02-07-C 02-07-D 02-07-E0x5A084FC6 0x587979DE 0xC960A68C03-10-D 03-14-C0xC2172756 0x3BE626FB
Postprocessing02-08-B 02-08-C 02-08-D0x2C4B20EC 0x459B14C1 0x6539743703-09-D 03-12-E0x816A45E3 0xDBEB2D99
Archive02-06-A 02-07-A 02-07-B0xB9652A43 0x420652AC 0x013C791903-10-D 03-10-P0xB6E506A1 0x384639C5
Modbus02-20-A 02-20-B 02-20-C0x9221E790 0xF4348ED8 0xF20B85FE03-12-B 03-17-A0x8E1DD57B 0x47A64C44

OIML Certificate

OIML Member State The Netherlands

Number R137/2012-A-NL1-20.07 revision 2

Project number 3572038

Page 4 of 6

Table 3 General characteristics of the family of instruments

Diameter sizeminimum Internal bore IDmin[mm]maximum Internal bore IDmax[mm]Minimum flow velocityVmin[1][m/s]Minimum Transitional flow velocityVt[1],[2][m/s]Maximum flow velocityVmax[1][m/s]
InchDN
410090102,30,492,337,6
6150139154,10,292,036,6
8200180206,40,292,139,2
10250230254,40,292,036,2
12300280311,20,301,533,8
143503053250,281,533,5
16400350393,70,301,533,6
18450387,1437,90,242,727,1
20500431,8488,90,301,631,1
225504895300,281,428,7
24600532,2590,90,301,530,4
26650609,2640,90,262,828,4
30750730,3742,90,252,929,5
36900850,5894,90,301,529,8

The corresponding flow rates can be calculated as follows:

Where:

Q = flow rate $ [\mathrm{m}^{3} / \mathrm{h}] $

V = velocity [m/s]

ID = inner diameter [m]

Notes:

[1] If higher values are chosen for $ Q_{\min} $ and/or lower values for $ Q_{\max} $ it has to be taken into account that: $ Q_{\min}\leq0,05 $ $ Q_{\max} $ and $ Q_{\min} / Q_{\max} > 5 $

$$ Q _ {\max } / Q _ {t} \geq 5. $$

[2] According to the manufacturers specification the following $ Q_{t} $ restrictions are applicable: for 1:20 $ \leq $ $ Q_{\min} $ $ / $ $ Q_{\max} $ 1:50 $ Q_{t} \leq 0,2\cdot Q_{\max} $ for 1:50 $ \leq $ $ Q_{\min} $ $ / $ $ Q_{\max} $ $ Q_{t} \leq 0,1\cdot Q_{\max} $

OIML Certificate

OIML Member State The Netherlands

Number R137/2012-A-NL1-20.07 revision 2 Project number 3572038 Page 5 of 6

Installation conditions:

Installation of the ultrasonic gas meter

For mild and severe flow disturbances the meter needs to be installed with the following minimum piping configuration as upstream inlet:

  • severe disturbances: 5D straight piping + flow conditioner + 5D straight piping.

  • mild disturbances: 5D straight piping.

The flow conditioner can be of the following types:

  • CPA50 type A

NOVA 50E

The outlet piping shall comply with:

3D straight piping (for both mild and severe disturbances).

Any components which could affect the gas flow must be avoided within the above prescribed inlet pipe length. The necessary straight pipe length is stated on the name plate of the meter. The inlet pipe must be designed as a straight pipe section of the same nominal diameter as the gas meter with a maximum tolerance of +/- 3%.

Bi-directional flow measurement

During conformity assessment it is sufficient to verify a bi-directional meter only in one direction.

Temperature sensor

The installation of a temperature sensor is at 2-5D from the outlet of the meter or of a dedicated measuring skid section (as described in chapter Measuring skid with two meters in series). For bidirectional applications, an additional temperature sensor can be installed 2-5D upstream of the meter or of a dedicated measuring skid section. The pipe spools including the thermo well(s) shall be installed and considered during the examination for putting into use of the gas meter.

Measuring skid with two meters in series

A conformity assessment is needed when the meter will be used in series with another ultrasonic meter (same or different type) and the length of the straight piping between the two meters is smaller than the minimum inlet or outlet length as mentioned in chapter 3.1 or if the meters are direct connected (flange to flange) to each other.

The conformity assessment has to be done on the complete measuring skid (USM package, including meter tubes, flow conditioner and thermowells) and the upstream meter must fulfill the inlet requirements of the downstream meter.

Alternative welded installation

The meters can be welded directly without flanges to the inlet and outlet pipes. The inlet and outlet pipe length shall be according the requirements as prescribed above for mild and/or severe disturbances. The complete meter package (meter including welded piping) shall be calibrated in order to guarantee compliance with Class 0.5.

OIML Certificate

OIML Member State The Netherlands

Number R137/2012-A-NL1-20.07 revision 2 Project number 3572038 Page 6 of 6

Interchangeable components:

The ultrasonic transducers mounts are an interchangeable component and can be replaced with units of the same type with additional gasket. After exchange of a part of the system, it is necessary to perform a functional test.

Certificate history:

This revision replaces the previous version.

RevisionDateDescription of the modification
Initial2 November 2020-
126 August 2021Revision due to new hardware: - Field terminal board version BD. - Main Board version AJ.
218 August 2022Addition of firmware V3.40.